UPSon - 33M Series |
|
20 kVA UPS Systems Technical Specifications |
|
|
Power (kVA) |
20 kVA |
|
Power ( kWatt ) |
16 kWatt |
|
Input Voltage |
380 / 400 / 415 VAC ; 3 Phase, N |
|
Input Voltage Range |
± 15% |
|
Input Frequency |
50 / 60 Hz |
|
Input Frequency Range |
± 10% |
|
Input Power Factor |
> 0,85 |
|
Output Power Factor |
0,8 |
|
Output Voltage |
380 / 400 / 415 VAC ; 3 Phase, N |
|
Output Voltage Regulation |
± 1% ( Static ) ;
± 5% ( Dynamic ) |
|
Output Frequency |
50 Hz / 60 Hz ( selectable ) |
|
Frequency Stability |
± 0,1% ( operation by battery ) ;
± 1% ( main synchron ) |
|
Voltage Wave |
Sinusoidal |
|
Total Harmonic Distortion |
< 3% ( lineer load ) ; < 5% ( non-lineer load ) |
|
Cold Start |
No |
|
Total Efficiency |
> 90% |
|
Crest Factor |
3 : 1 |
|
Transfer Time |
0 msec. |
|
Battery Type |
No maintenance battery |
|
Battery Unit |
30 |
|
Charge Voltage |
405 VDC |
|
Deep Discharge Voltage |
300 VDC |
|
Battery Test |
Automatic and manuel battery test system |
|
Battery Charge Time |
8 hours to 90% capacity after deep discharge |
|
Type |
LCD Alphanumerical mini panel |
|
LCD Display |
Input Voltage , Output Voltage , Battery Voltage, Battery Current, Output Frequency, Battery Charge Level, UPS Power, Load Percent, Synchron Case, Communication systems fault info. |
|
LED Display |
Load on Bypass, Load on UPS, Alarms and operation by battery leds. |
|
Over Load Capacity |
100% ~ 125% load 10 minutes ; 125% ~ 150% load 1 minute ; > 150% load on the bypass |
|
Short Circuit |
a) Inverter mod: UPSis shutdown itself
b) Bypass mod : AC protection fuse is blow |
|
Over Heat |
a) If main normale : UPS is cross to by-pass mode
b) If main voltage is not normale : UPS is cut output, Alarm on the LCD Display. |
|
Battery Low Level |
Battery low alarm occurs on the LCD. Sound alarm is given after 15 second |
|
Visual and Auditory |
Bypass alarm, mains fault, load on bypass, overload, mains failure, output voltage high / low, over temperature, battery voltage high/low, short circuit, fault inverter, battery test
( Buzzer can be Off.) |
|
Management |
Dry contact info, RS232 Serial Port, TMON Software, remote control panel ( option ), SNMP and Megatec protocol ( option ) |
|
Dry Contact Information |
Load on inverter / Bypass, Operation battery / mains, Battery low / normale, emergency button |
|
HTTP / SNMP Harmony |
Windows 95/98/NT/XP, UNIX, LINUX, NOVELL, Netware, OS/2, Netlite, XENIX, AIX, MS-DOS, HP-UX, SUN OS ( Software CD and cable ) |
|
Noice Level |
< 60 to 62 dB ( 1 Meter ) |
|
Technologic |
High frequency IGBT technology, PWM, True Online System, 2 Micro Pro. and high protection by driver |
|
Operation Temperature / Humidity |
0 °C ~ +40 °C / Maximum 90% |
|
Cooliing |
Fan |
|
Dimension WxHxD ( mm ) |
490 x 1200 x 680 |
|
Weight |
~ 270 kg |
|
|
Security ( EN50091-1 ) / EMC ( EN50091-2 ) / IP Class ( IP 20 ) / VFI Class ( IEC62040-3 ) |
|
|
Parallel kit, SNMP kit, seperate main input, remote pannel, Philters, 12 Pulse rectifier, temperature control rectifier, RS485, ECO Mod. |
Not: All the information mentioned above is provided for the purpose of being a reference. The right to change without notice to third parties is reserved. ©2007